LOW-ΔP-FLOW series |
|
Accuracy (incl. linearity) (based on actual calibration) |
± 1% FS (of Full Scale) |
Turndown |
1 : 50 (2~100%) |
Repeatability |
< 0,2% Rd |
Settling time (controller) |
standard: 2~3 seconds |
Operating temperature |
-10~+70°C ( for ATEX cat. 3 max. 50°C ) |
Temperature sensitivity |
0,1% FS/°C |
Pressure sensitivity |
0,1% Rd/bar typical N2 |
Mounting position |
horizontal |
Warm-up time |
30 min. for optimum accuracy / 2 min. for accuracy ± 2% FS |
Power supply |
+15~24 Vdc |
Analog output/command |
0~5 (10) Vdc or 0 (4)…20 mA (sourcing output) |
Digital communication |
standard: RS232 / options: DeviceNet™, CANopen®, PROFIBUS®DP, Modbus RTU/ASCII, FLOW-BUS, EtherCAT®, PROFINET, Modbus-TCP, EtherNet/IP, POWERLINK |
Control stability |
< ±0,1% FS (typical for 1 ln/min N2) |
어플리케이션 |
• 대기 조건에서의 환경 공기 샘플링
• 누출률(Leak) 테스트
• 가스 소비량 측정 ( 천연가스, 저압 가스 분배시스템)
• 연소기 컨트롤 |
LOW-ΔP-FLOW Series
l 산업용 하우징 (IP65)
Mass Flow Meter (MFM) |
Ranges |
Series F-100D |
min.
0,2 ~ 10 mln/min |
Series F-101D |
min.
0,42 ~ 21 mln/min |
Series F-101E |
min.
0,028 ~ 1,4 ln/min |
Series F-102E |
min.
0,17 ~ 8,5 ln/min |
Series F-103E |
min.
0,9 ~ 45 ln/min |
Mass Flow Meter (industrial execution – IP65) |
Ranges |
Series F-100DI |
min.
0,2 ~ 10 mln/min |
Series F-101DI |
min.
0,42 ~ 21 mln/min |
Series F-101EI |
min.
0,028 ~ 1,4 ln/min |
Series F-102EI |
min.
0,17 ~ 8,5 ln/min |
Series F-103EI |
min.
0,9 ~ 45 ln/min |
Series F-106Z/F-107Z |
min.
0,2 ~ 10 m3n/h |
Mass Flow Meter (Standard execution) |
Ranges |
Series F-200DV |
min.
0,2 ~ 10 mln/min |
Series F-201DV |
min.
0,42 ~ 21 mln/min |
Series F-201EV |
min.
0,028 ~ 1,4 ln/min |
Series F-202EV |
min.
0,17 ~ 8,5 ln/min |
Typical combinations of Mass Flow Meters with close coupled Control Valves ( standard execution ) |
Ranges |
F-102E + F- 004AC-LU |
up
to to 1 ~ 50 ln/min; |
F-103E + F- 004BI-IV |
up
to 4 ~ 200 ln/min; |
Mass Flow Controllers ( industrial execution -IP65 ) |
Ranges |
Series F-200DI |
min.
0,2 ~ 10 mln/min |
Series F-201DI |
min.
0,42 ~ 21 mln/min |
Series F-201EI |
min.
0,028 ~ 1,4 ln/min |
Series F-202EI |
min.
0,17 ~ 8,5 ln/min |
Typical combinations of Mass Flow Meters with close coupled Control Valves ( industrail execution – IP65 ) |
Ranges |
F-102EI + F- 004AI-IU |
up
to 1 ~ 50 ln/min; |
F-103EI + F- 004BI-IV |
up
to 4 ~ 200 ln/min; |